A.PERFORMANCE [Room Temp at 20ºC, Air Cooled Type]
Temp & Hum Control Range See Graph below
B.STRUCTURE
1.Interior Material: Stainless Steel Plate (SUS#304)
2.Exterior Material: A3 Steel Plate sprayed with special coating
3.Insulation Material:Double-layer, High Temperature resistant and high Intensity seal is applied between the chamber door and chamber body to ensure high performance
4.Heater: Fin Heat Disperse Pipe Stainless Steel-Electric Heater
5.Humidifier: Stainless Steel Heater with Auto Adjust
6.Airflow Cycling System: Unique System for providing uniform airflow
7.Door & Window: Single Door with Observation Window, (Heating cords set around the door to prevent Condensation)
C.REFRIGERATION SYSTEM
1.Compressor Hermetic Compressor - 2HP, Tecumseh
Option B: two compressors;
Option C: two compressors;
Option D: two compressors
2.Refrigerant Type: DuPont Type 404A (Without Fluorine)
3.Condenser: Air Cooled with Fan
4.Evaporator: Fin with several segments –Auto adjustment
D.CONTROLLER PROGRAMMABLE COLOR LCD Model TEMI 800
1.Controller Specifications LCD DISPLAY COLOR TOUCH SCREEN KEY IN
User friendly Color-LCD interactive touch-screen system powerful controller with several Programmable and Fixed Value features such as:
100 Programs and 1200 Segments with Run time of 99H 59M ea. to set up
Temp-Hum profiles per user requirements.
Data Storage and profile recall
Communications: RS485/RS232 - PC Interface
2.Control Panel
a.Lighted Push Button switch for POWER
b.Lighted Push Button for chamber lighting
c.RS232/485 port for PC interface
d.Over Temperature protector – Manually settable
e.Emergency reset switch (EMO)- Optional
E.SAFETY DEVICES
a.Ground protection
b.Three phase Over voltage, Under voltage, Phase loss and Phase Sequence Protection
c.Leakage/Circuit protection
d.Heater and Humidifier heater short-circuit protection
e.Circulation Fan motor overload protection
f.Compressor Overload protection
g.Compressor High Pressure protection
h.Independent over-temperature alarm system
i.Lack of Water protection (Humidification)
j.Circuit breaker
k.Emergency Shut Off Switch (EMO)-Optional
F.ACCESSORIES
a.Cable Access:One (2”) (50mm) cable access port with plug
b.Temp-Humidity Sensors:SUS #304L stainless steel PT 100Ω platinum resistance
c.AC Power Cord:Low Impedance ,Length 2.5m
d.Shelves:Two Sets of Stainless Steel Shelves with adjustable Brackets
e.Door Sealing:Environmentally safe Silicone rubber which is high temperature resistance,aging resistance,with excellent good sealing capability
f.Casters:Heavy Duty – Set of 4 (adjustable mobile casters)
g.Humidity Sensing method: Wet and dry bulb
h.Water Supply:Internal Water Tank Water Inlet Valve
G.FACILITIES
POWER:220VAC/50/60Hz/Single Phase/15A/6.0KW
Chamber Environment:
Temperature: 5~28C Humidity: <85%
No.22, Hanyuan Road,Xincheng District,Xi'an,China
TEL: 0086-29-85451431
Email: sales@ace-climatic.com